hvac, space heaters, heaters, industrial, space heating, heating systems

heat, hvac, space heaters, propane heaters, heating, swimming pool heaters, reznor
 
l l l l l l
 
 
 
Qualified for Energy Technology List - www.eca.gov.uk
 
 
V3 - The most exciting innovation in gas fired unit heaters for many years. Reznor’s extensive research and development has resulted in a technically advanced range of unit heaters that deliver the highest possible standards of energy efficiency and performance.
Incorporating a radical new heat exchanger and burner V3 is compact, lightweight and provides end users, consulting engineers and installation contractors with the ultimate unit heater solution.
 
Energy Saving
4-pass heat exchanger achieves over 92% thermal efficiency.
Reduced carbon dioxide and NOx emissions.
Eligible for 100% enhanced capital allowances.
Improved airflow and new louvre design give longer air throws and significantly reduces stratification within the building.
Aerodynamic heat exchanger profile enables up to 20% increase in airflow with a 30% reduction in electrical consumption.
   
Easy Installation and Maintenance
Up to 37% lighter than comparative models.
Balanced flue wall terminal provides both flue outlet and combustion air inlet thereby reducing installation time.
Balanced flue units eliminate the need for combustion air grilles in the wall.
Application Versatility
Both horizontal and vertical down flow
(combined heating/ destratification) units are available.
The smallest unit is only 310mm high - Making it ideal for mounting in confined areas e.g. underneath mezzanine floors.
 
     
   
V3 is suitable for a wide range of applications - industrial and commercial premises; retail; sports and leisure; warehouses, logistics and distribution centres.
Vertical downflow models are ideal for warehouse heating.
 
Enhanced Safety
Room sealed units draw combustion air from outside the building thereby preventing contaminants from entering the combustion zone.
 
Extended Operational Life
The titanium stabilised aluminised steel heat exchanger is particularly strong and durable providing additional temperature resistance. Its weld free construction ensures long life.
 
 
MODEL UDSA 008 UDSA 011 UDSA 015 UDSA 020 UDSA 025 UDSA 030 UDSA 035 UDSA 043 UDSA 050 UDSA 055 UDSA 064 UDSA 073 UDSA 0085 UDSA 100
Nominal heat output kW 7 11 15 18 26 29 35 42 49 55 64 73 85 97
Airflow m³/h 680 1020 1360 1700 2385 2725 3510 4535 5180 5830 6810 7770 9065 10360
Temperature rise 0C 32 32 32 32 32 32 31 28 28 28 28 28 28 30
Throw (1) m 8 10 13 16 20 22 25 28 30 30 33 35 36 39
Noise Level (free field @ 5 metres) dB(A) 40 39 40 41 43 44 48 50 51 52 53 53 53 54
Noise Level (typical installation @ 5 metres) dB(A) 47 46 47 48 50 51 55 57 58 59 60 60 60 61
Gas consumption(2) Nat Gas G20 m³/h 0.84 1.26 1.68 2.1 2.94 3.36 4.03 4.85 5.59 6.3 7.41 8.4 9.8 11.19
Propane G31 kg/h 0.63 0.94 1.26 1.57 2.2 2.51 3 3.66 4.18 4.71 5.5 6.27 7.32 8.37
Gas connection(3) Rc 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Mounting Height(4) m 2.0-2.5 2.0-2.5 2.0-3.0 2.0-3.0 2.0-3.5 2.0-3.5 2.5-3.5 2.5-3.5 2.5-3.5 2.5-3.5 3.0-4.0 3.0-4.0 3.0-4.0 3.0-4.0
Total electrical rating (230V/50Hz) kW 0.12 0.12 0.13 0.13 0.27 0.27 0.35 0.37 0.43 0.49 0.68 0.85 0.85 0.85
Net weight kg 30 33 38 40 56 60 88 99 99 112 118 143 158 168
 
  Note: 1. Isothermic condition (20°C). Throw is dependent on mounting height, building height, room
temperature and louvre settings.
  2. Natural gas G20 Calorific value 10.5 kWh m3GCV, inlet gas pressure maximum 50mbar, minimum 17.5mbar.
Propane G31 Calorific value 14.0 kWh/kg GCV, inlet gas pressure maximum 50mbar, minimum 37mbar.
  3. Not supply line size.
  4. Recommended height to underside of heater for standard horizontal discharge units. Downturn nozzles are recommended for units installed at the higher mounting height. Please consult Reznor.
   
 
 
MODEL UDSA 008 UDSA 011 UDSA 015 UDSA 020 UDSA 025 UDSA 030 UDSA 035 UDSA 043 UDSA 050 UDSA 055 UDSA 064 UDSA 073 UDSA 085 UDSA 100
A 310 310 385 385 590 590 510 510 510 665 665 865 865 865
B 675 675 675 675 675 675 970 970 970 970 970 1040 1040 1040
C (1) 415 415 415 415 415 415 625 625 625 625 625 675 675 675
D 660 660 685 700 725 745 1070 1070 1070 1140 1140 1150 1150 1150
E(1) 350 350 350 350 350 350 600 600 600 600 600 600 600 600
F 100 100 100 100 100 100 150 150 150 150 150 150 150 150
G(1) 413 413 622 622 622 622 622 672 672 672
H(1) 250   450   400 400 400 500 500 500 500 500
Flue outlet dia J 80 80 80 80 100 100 100 100 100 130 130 130 130 130
Air inlet dia K 80 80 80 80 100 100 100 100 100 130 130 130 130 130
Top clearance 50 50 50 50 50 50 100 100 100 100 100 100 100 100
Rear clearance 450 450 450 450 450 450 450 450 450 450 450 450 450 450
Bottom clearance 50 50 50 50 50 50 100 100 100 100 100 100 100 100
Side clearance 50 50 50 50 50 50 50 50 50 50 50 50 50 50
Access clearance 850 850 850 850 850 850 850 850 850 850 850 850 850 850
 
  Note: 1. = Suspension centres.
*Clearance required for combustibles - units may be base mounted on suitable non-combustible supports.
All dimensions in mm.
  Only highlighted products are available as downflow units - ( UDSA 015, 025, 035, 043, 050, 055, 064, 073
085, 100 )
   
   

Tel.. 01303 259141

Fax.. 01303 850002

sales@reznor.co.uk

An Ambi-Rad Group Company