hvac, space heaters, heaters, industrial, space heating, heating systems

heat, hvac, space heaters, propane heaters, heating, swimming pool heaters, reznor
l l l l l l
 
 
 
Qualified for Energy Technology List - www.eca.gov.uk
UPA gas fired unit heaters deliver low cost energy efficient heating. With a range of outputs from 27 to 91kW units offer very high thermal efficiencies and are suitable for both industrial and commercial heating applications. Furthermore all units incorporate a power-vented flue to help eliminate unnecessary heat loss via the flue system in order to improve seasonal efficiencies.  
 
 
 
Cost savings
High efficiency models achieve thermal efficiencies of 92% and are listed on the governments energy technology list.
(End users who purchase products on this list are eligible to claim 100% Enhanced Capital Allowances within the
1st year).
Fast pay back - the reduced energy consumption, and reduced installation costs, allows the capital cost of higher
efficiency units to be recovered within twelve months.
Low cost
 
Features
Power vented flue
Axial fan for free blowing applications
Aluminised steel heat exchanger
Suitable for natural gas (G20)
Horizontal louvres
Auto spark ignition system
High thermal efficiency 92% net CV
Options
Vertical louvres
Downturn nozzles (30° and 60°)
Suitable for propane gas
Economy thermostat
Wall mounting brackets
   
Energy Saving
High efficiency operation results in lower running costs
Longer air throw improves distribution
Easy Installation
Power vented rear flue outlet permits use of
a simple wall terminal removing the requirement for roof penetrations.
 
 
MODEL unit UPA 30 UPA 40 UPA 50 UPA 60 UPA 70 UPA 90
Nominal Heat output kW 27 40 49 57 69 91
Air flow (@ 15°C) m³/h 2385 3885 4535 5540 6810 8825
Temperature rise K 33 30 32 30 29 30
Throw (1) m 20 25 28 30 33 36
Maximum Flue length (2) m 14 14 14 14 14 14
Gas Consumption nat.gas G20 (3) m³/h 3.12 4.60 5.69 6.50 7.83 10.48
propane G31 (4) kg/h 2.30 3.39 4.20 4.79 5.77 7.72
Gas connection (5) Rc 1/2 3/4 3/4 3/4 3/4 3/4
Fan motor(s) rating kW 0.12 0.18 0.34 0.34 0.53 0.69
Total electrical rating kW 0.273 0.333 0.490 0.490 0.677 0.848
Sound pressure level (Lp)@5m free field dB(A) 43 45 49 52 49 53
typical
installation
dB(A) 50 52 56 59 56 60
Suggested mounting
height (6)
m 3.5 3.5 3.5 3.5 4 4
Approximate weight kg 56 93 104 114 123 163
 
  1. Throw depends on height of building, mounting height of heater, room temperature and louvre settings
  2. Deduct 1.5 metres for each 90 degree bend
  3. Natural Gas – minimum inlet pressure 17.5 mbar, maximum inlet pressure 50mbar
  4. Propane Gas – minimum inlet pressure 37 mbar, maximum inlet pressure 50mbar
  5. Not supply line size
  6.To underside of heater
   
 
   
 
   
 
   
 
 
MODEL unit UPA 30 UPA 40 UPA 50 UPA 60 UPA 70 UPA 90
Width A 702 975 975 975 975 1045
Height B 588 512 512 665 665 868
Overall length C 774 1132 1152 1141 1141 1141
Cabinet length D 549 900 900 900 900 900
Flue outlet diameter E 100 100 100 130 130 130
Base to flue outlet G 368 372 372 355 355 564
Base to gas inlet J 222 126 126 145 145 300
Side to gas inlet L 124 166 166 166 166 187
Side to flue outlet M 193 195 195 207 207 213
Suspension centres N 413 622 622 622 622 672
Suspension centres P 350 600 600 600 600 600
Side to suspension point Q 17 37 37 37 37 37
Back to suspension point R 98 150 150 150 150 150
Top clearance V 50 100 100 100 100 100
Access side clearance W 850 850 850 850 850 850
Side clearance X 50 100 100 100 100 100
Rear clearance Y 450 450 450 450 450 450
 
  All dimensions in mm.
   
   

Tel.. 01303 259141

Fax.. 01303 850002

sales@reznor.co.uk