| Euro-T2000 series is a range of fully
automatic room sealed gas fired unit heaters, for
industrial and commercial applications, particularly
suited where draughts, negative pressure, dust or other
non corrosive contaminants may be present. At the heart of
the heaters is the perfectly co-ordinated combination of
heat exchanger and burner, developed and patented by
Reznor, that has set the standard for efficiency,
reliability and operational life.
The
combustion process is completely separated from the
heated space. An integral flue gas fan exhausts the
products of combustion and at the same time introduces
fresh air from outside the building for combustion.
This
separated combustion technology, pioneered by Reznor,
offers major advantages:
| |
|
|
Higher
thermal efficiencies - up to 82% based on gross
calorific values |
| |
|
|
Higher
seasonal efficiencies - loss of heated room air
via a conventional flue |
| |
|
|
is
eliminated |
| |
|
|
Lower
installation costs - balanced flue system
requires no additional |
| |
|
|
ventilation
openings in external walls and may be flued via a
simple wall |
| |
|
|
terminal
avoiding the need for any roof flashings |
| |
|
|
Improved
reliability - hot surface ignition system
eliminates pilot problems |
| |
|
|
Optional
low NOx units may be specified if required |
Units are available in capacities from 23 to 95
KW. Standard models suitable for natural gas are equipped
with aluminised steel heat exchangers, automatic ignition
systems, single phase motors and have the flue and
combustion air spigots located on the top of the heater.
A
comprehensive range of options allows the units to be
tailor made to suit extensive application requirements.
Options include stainless steel heat exchangers, vertical
louvres, 30, 60 and 90 degree downturn nozzles and units
suitable for use on LPG. The heaters may also be provided
with the flue and combustion air spigots located on the
side to allow complete flexibility of flueing.
For
closer temperature control and reduced stratification,
units may be specified with high/low or fully modulating
burner control.
Reznor
microprocessor energy management controls are available
to complement the energy efficient heaters and optimise
fuel economy.
EURO-T2000S
The standard axial fan
versions are designed for freeblowing industrial and
commercial applications.
Units
are equipped with high quality axial flow fans to provide
good air distribution at low noise levels. Standard
models are supplied with aluminised steel heat
exchangers, hot surface ignition and horizontal louvres.
Since
the units are room sealed, they do not require the
installation of air grilles to the external walls.
EURO-T2000A
The high performance axial
fan models are designed for freeblowing industrial and
commercial applications where higher mounting heights are
required. The units are fitted with an extended fan
plenum chamber and a large diameter axial flow fan to
provide substantially increased airflows. A high
induction discharge head complete with both horizontal
and vertical discharge louvres improves the air mixing
and increases the air throw to ensure minimal
stratification and uniform air distribution and
temperatures within the building. The units may be used
in place of heaters fitted with lower airflow direct
drive centrifugal fans to provide improved air
distribution at lower noise levels.
The
aesthetically pleasing design and improved air
distribution ideally match the criteria for new low
energy buildings.
EURO-T2000B
Type-B
models are fitted with belt driven, centrifugal blowers
and a duct outlet spigot to allow the units to be
connected to air distribution ductwork. The large
capacity forward curved centrifugal fans are mounted on
an angled plenum chamber to optimise the air distribution
across the heat exchanger, and a selection of motor and
drive configurations enables the units to match a wide
range of airflow and static pressure requirements.
The units are also ideal
where freeblowing heaters are required at very high
mounting heights. Use of the high capacity belt driven
fans allows much higher airflows to be selected to ensure
correct air distribution to the working zone. A range of
outlets complements the choice of airflows. The high
induction louvre, complete with horizontal and vertical
louvres, may be selected, or downturn nozzles which can
be used in multiples to provide 30, 60, 90 degree
discharge.
Type
D Downflow Plenum. For centrifugal
fan units where a vertical downflow discharge is
required, units may be fitted with a Type D outlet. This
downflow head is fitted with four individual sets of
louvres which may be adjusted to give the precise air
pattern required in two, three or four directions.
EURO-T2000E
Designed
to meet a wide range of air handling applications, these
units are supplied with forward curved centrifugal fans
enclosed in an internally insulated fan cabinet. The fan
cabinet may be fitted with a variety of filter options
and also allows for the connection of recirculation
ductwork. Comprehensive drive and motor options allow a
range of airflows and duties to be specified to suit duct
system design up to 400Pa.
All models are fitted to a
base frame which can be floor mounted or from which the
units can be simply suspended using the four suspension
points provided. Units are supplied as standard with an
outlet spigot for connection to duct work, but may also
be used with the optional outlet heads for freeblowing
applications.
A
range of options, including high/low or modulating burner
control, air flow proving or dirty filter pressure
switches and constant fan facility, ensure optimum system
design. Since the units are room sealed they do not
require the installation of combustion air grilles to the
external walls of the plant room.
Units
are also available for combined heating and ventilation
applications where fresh air is required either in Winter
or for Summer ventilation.
Where
units are used to provide ventilation, stainless steel
heat exchangers (AISI 409) are recommended. Dampers may
be fitted to the back, top or bottom of the cabinet.
Dampers fitted on the back and top, or back and bottom,
may be linked to allow the cabinet to be used as a mixing
box for fresh and recirculated air. Fully automatic
operation may be achieved using two position, three
position or fully modulating damper actuators, or
alternatively, the dampers may be manually controlled.
Fully modulating burner
control is particularly beneficial when winter
ventilation is required. A modulating control allows
units to be used as conventional heaters which can then
provide tempered fresh air input once the space reaches
design temperature.
Where
make-up or ventilation air is used a fast response
ignition system should be specified.
Euro-T
Technical Data
| Model |
|
|
T2025 |
T2030 |
T2035 |
T2045 |
T2055 |
T2075 |
T2095 |
| Heat Output |
|
kW |
22.8 |
27.8 |
33.7 |
39.4 |
49.9 |
68.3 |
91.0 |
| Gas
consumption1 |
Nat Gas G20 |
m3/h |
2.75 |
3.36 |
4.07 |
4.76 |
6.03 |
8.25 |
11.01 |
| |
Propane G30 |
kg/h |
2.06 |
2.51 |
3.05 |
3.56 |
4.51 |
6.18 |
8.24 |
| |
Butane G31 |
kg/h |
2.10 |
2.57 |
3.12 |
3.64 |
4.61 |
6.31 |
8.42 |
| Gas
connection2 |
|
Rc |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
| Flue
diameter |
|
mm |
100 |
100 |
100 |
130 |
130 |
130 |
130 |
| Combustion
air inlet diameter |
|
mm |
100 |
100 |
100 |
130 |
130 |
130 |
130 |
| Wall Opening |
|
mm |
140 |
140 |
140 |
185 |
185 |
185 |
185 |
| Roof Opening |
|
mm |
150 |
150 |
150 |
200 |
200 |
200 |
200 |
Maximum
flue length
Class C appliance3 |
|
m |
9 |
9 |
9 |
9 |
9 |
9 |
9 |
Axial
Fan Freeblowing Models T2000S & T2000A
| T2000S |
|
|
T2025S |
T2030S |
T2035S |
T2045S |
T2055S |
T2075S |
T2095S |
| Airflow @
15oC |
|
m3/h |
1700 |
2400 |
3700 |
3700 |
4200 |
5600 |
7900 |
| Temperature
Rise |
|
K |
39 |
34 |
27 |
32 |
35 |
36 |
34 |
| Throw4 |
|
m |
17 |
20 |
28 |
28 |
28 |
32 |
38 |
| Mounting
Height5 |
|
m |
2.0-2.5 |
2.25-2.75 |
2.5-3.0 |
| Sound
pressure level Lp6 |
|
dB(A) |
53 |
52 |
55 |
55 |
55 |
56 |
59 |
| Fan motor
rating |
|
kW |
0.075 |
0.120 |
0.120 |
0.120 |
0.120 |
2 x 0.120 |
2 x 0.120 |
| Total
electrical rating7 |
|
kW |
0.25 |
0.28 |
0.37 |
0.37 |
0.36 |
0.45 |
0.65 |
| Net weight |
|
kg |
86 |
92 |
108 |
108 |
130 |
150 |
195 |
| Shipping
weight |
|
kg |
109 |
115 |
137 |
137 |
162 |
190 |
237 |
| T2000A |
|
|
T2025A |
T2030A |
T2035A |
T2045A |
T2055A |
T2075A |
T2095A |
| Airflow @
15oC |
|
m3/h |
2500 |
3100 |
4000 |
4000 |
5600 |
7300 |
8700 |
| Temperature
Rise |
|
K |
26 |
26 |
25 |
29 |
26 |
27 |
31 |
| Throw4 |
|
m |
26 |
26 |
31 |
31 |
32 |
37 |
46 |
| Mounting
Height5 |
|
m |
2.5-3.25 |
2.5-3.5 |
2.75-4.0 |
3.0-4.25 |
3.0-4.5 |
| Sound
pressure level Lp6 |
|
dB(A) |
55 |
56 |
55 |
55 |
59 |
59 |
60 |
| Fan motor
rating |
|
kW |
0.20 |
0.23 |
0.24 |
0.24 |
0.40 |
0.37 |
0.56 |
| Total
electrical rating7 |
|
kW |
0.35 |
0.38 |
0.40 |
0.40 |
0.55 |
0.52 |
0.71 |
| Net weight |
|
kg |
101 |
112 |
142 |
142 |
157 |
200 |
232 |
| Shipping
weight |
|
kg |
125 |
136 |
171 |
172 |
191 |
239 |
277 |
Centrifugal
fan models T2000B & T2000E
| T2000B |
|
|
T2025B |
T2030B |
T2035B |
T2045B |
T2055B |
T2075B |
T2095B |
| Airflow @
15oC |
|
m3/h |
2100 |
2600 |
3700 |
3700 |
4700 |
6300 |
8400 |
| Temperature
Rise |
|
K |
32 |
31 |
27 |
31 |
31 |
32 |
32 |
| Throw4 |
|
m |
24 |
25 |
31 |
31 |
32 |
34 |
47 |
| Mounting
Height5 |
|
m |
2.5-3.25 |
2.5-3.5 |
2.75-3.75 |
3.0-4.0 |
3.0-4.25 |
| Sound
pressure level Lp6 |
|
dB(A) |
55 |
52 |
55 |
55 |
59 |
59 |
59 |
| Fan motor
rating |
|
kW |
0.18 |
0.18 |
0.25 |
0.25 |
0.37 |
0.55 |
0.75 |
| Total
electrical rating7 |
|
kW |
0.50 |
0.50 |
0.55 |
0.55 |
0.68 |
0.93 |
1.15 |
| Net weight |
|
kg |
108 |
135 |
155 |
155 |
168 |
193 |
248 |
| Shipping
weight |
|
kg |
133 |
160 |
195 |
195 |
210 |
240 |
298 |
| T2000E |
|
|
T2025E |
T2030E |
T2035E |
T2045E |
T2055E |
T2075E |
T2095E |
| Airflow @
15oC |
Min |
m3/h |
1350 |
1650 |
2000 |
2300 |
2900 |
4000 |
5400 |
| Max |
m3/h |
3000 |
4000 |
5000 |
5000 |
7200 |
9000 |
12000 |
| Fan motor
rating |
Min |
kW |
0.18 |
0.18 |
0.18 |
0.18 |
0.25 |
0.25 |
0.25 |
| Max |
kW |
1.1 |
1.1 |
1.5 |
1.5 |
2.2 |
3.00 |
3.00 |
| Total
electrical rating7 |
|
kW |
Fan Motor rating plus 0.15kW |
| Net weight8 |
|
kg |
138 |
169 |
200 |
200 |
221 |
267 |
319 |
| Shipping
weight8 |
|
kg |
158 |
191 |
222 |
222 |
244 |
298 |
353 |
Appliances
with higher efficiency
| Model |
|
|
T2026 |
T2031 |
T2036 |
T2046 |
T2056 |
T2076 |
T2096 |
| Heat Output9 |
|
kW |
23.7 |
28.8 |
35.0 |
41.0 |
51.9 |
71.0 |
94.6 |
Notes:
1. Natural
gas G20 - calorific value 10.48 kWh/m3 GCV, 15oC
1013 mbar. Propane G31 - Calorific value 14.0 kWh/kg GCV.
Butane G30, calorific value 13.7 kWh/kg GCV.
2. Not supply line size.
3. Maximum additional lengths that may be added to
terminal section. Deduct 1.5m for each 90o
elbow installed.
4. Isothermic condition, throw decay to 0.5m/s, discharge
louvres zero deflection
5. To underside of heater.
6. Typical installation; Q=2, A=160m2,
distance 5m, discharge louvres zero deflection.
7.During start up period (approx. 30 seconds) load is
increased by an additional 900W
8. Varies depending on motors & options fitted.
9. All other data is the same as standard models,
temperature will rise depending on airflow selected.
SPECIFICATION
CABINETS
All components are manufactured from aluminised steel and
exterior panels have a durable epoxy powder coat finish.
HEAT
EXCHANGER
Patented Thermocore venturi tube heat exchanger assembly
with precision matched burners provide optimum efficiency
and enhanced operational life.
Standard units are fitted with heat exchangers
manufactured from special grade aluminised steel. For
applications where fresh air is supplied through the
unit, stainless steel heat exchangers (AISI 409) are
recommended. Where chlorinated vapours or certain other
contaminants may be present, AISI 316 stainless steel
heat exchangers must be used; consult Reznor for such
special applications.
GAS AND
SAFETY CONTROLS
All units are tested and approved to current European
standards and are CE marked. A multi-functional gas
control valve and a fully automatic ignition system
provide full safety monitoring of the heater operation.
Fan operation is controlled by an integral fan control
which delays fan start up until the unit has reached
operating temperature and continues to operate the fan
after the burners have shut off, until all useful heat
has been dissipated into the building.
For additional safety, all Reznor units are fitted with
dual safety limit controls.
AIR
HANDLING
Axial fan models are fitted with direct drive axial flow
fans and single phase 230V, motors. Centrifugal fan
models are fitted with double inlet forward curved
centrifugal blowers and a belt drive with an adjustable
motor pulley, to allow small on-site adjustments to be
made. Motors may be single or three phase depending on
the duty requirements up to 400Pa resistance.
INSTALLATION
Installation must be carried out by a CORGI registered
installer in accordance with the manufacturer's
instructions.
Units may be suspended or base mounted on a non
combustible surface.
The units are approved as room sealed. In order to comply
with the CE certification, the heaters must be used with
the manufacturer's sealed flue system. Standard units are
supplied with the flue and air inlet spigots on top of
the heater; as an alternative, units may be supplied with
the spigots on the side.
Flue
systems are available for either wall or roof
penetrations. The concentric balanced flue terminal
provides both the flue outlet and combustion air inlet
from a single opening in the building.
A gas
isolation valve must be fitted adjacent to each unit. An
electrical isolator is also required, but the electrical
supply to the units should not be switched off except for
maintenance. Controls must be wired to the appropriate
time and temperature terminals and must not switch the
main electrical supply otherwise the control sequence of
the heater will be affected.
SUGGESTED FLUE ARRANGEMENTS
The
balanced flue terminal provides both the
combustion air inlet and flue outlet from a
single building penetration. The terminals are
ordered separately from the heaters to suit
either a wall outlet or roof outlet. Additional
flue and combustion air pipes may be added, up to
the maximum length stated in the data table.
Optional side flue outlet.
|
Standard top flue outlet
|
DIMENSION
DATA
T2000S Dimension diagram
T2000A Dimension diagram
T2000B Dimension diagram
T2000E Dimension diagram
| Model |
|
T2025 |
T2030 |
T2035 |
T2045 |
T2055 |
T2075 |
T2095 |
| Cabinet
width |
A |
520 |
590 |
730 |
730 |
870 |
1080 |
1360 |
| Overall
width (E model) |
B |
524 |
594 |
734 |
734 |
874 |
1084 |
1364 |
| Duct inlet
width (E model) |
C |
370 |
440 |
580 |
580 |
720 |
930 |
1213 |
| Suspension
centres (E model) |
D |
436 |
506 |
646 |
646 |
786 |
996 |
1276 |
| Suspension
centres (S, A & B models) |
E |
359 |
429 |
569 |
569 |
709 |
919 |
1199 |
| Duct outlet
spigot width |
F |
360 |
430 |
570 |
570 |
710 |
920 |
1200 |
| Side
clearance |
G |
150 |
150 |
150 |
150 |
150 |
300 |
300 |
| Access side
clearance |
H |
550 |
620 |
750 |
750 |
900 |
1100 |
1400 |
| Heater back
to air inlet |
J |
166 |
166 |
166 |
90 |
90 |
90 |
90 |
| Air
inlet/flue outlet centres |
K |
140 |
140 |
140 |
140 |
225 |
225 |
225 |
| Flue outlet
diameter |
L |
102 |
102 |
102 |
132 |
132 |
132 |
132 |
| Air inlet
diameter |
M |
102 |
102 |
102 |
132 |
132 |
132 |
132 |
| Depth
centrifugal fan (B model) |
N |
518 |
575 |
668 |
668 |
668 |
575 |
668 |
| Depth axial
fan (S model) |
P |
197 |
235 |
240 |
240 |
240 |
235 |
240 |
| All