RPVE 2000 WALL MOUNTED GAS FIRED HEATER
The RPVE2000 "wall mounted" heater is a compact
lightweight fully automatic gas fired heater designed to complement
the existing RPV2000 range. Due to its reduced size and weight, the
unit can be mounted externally on the wall and is supplied with an
integral base frame and wall brackets for easy mounting.
As with all RPV models the unit is designed to provide heating or
make-up air for industrial and commercial buildings. The unit has high
efficiency (up to 91% based on net c.v.) and low NOx options available
and because it is wall mounted provides a simple low cost easy to
install and maintain solution.
|
|
|
RPVE2000 WM units are available in 4 sizes with heat outputs
between 40 and 95kW. They are available in standard and high
efficiency models (88% & 91% based on net c.v.) with both
available in low NOx options.
|
|
|
Standard Features
- Units suitable for natural gas
- Stainless steel heat exchanger (AISI 409)
- Single stage burner control
- Automatic hot surface ignition
- Pre-painted galvanised base frame and wall
mounting brackets
Optional Features
- Units suitable for LPG
- High grade stainless steel heat exchanger (AISI 316)
- Two stage or fully modulating control
- Constant running fan relay
- Remote time and temperature controls
- Insulated blower cabinet
- High efficiency units
- Low NOx units
|
|
|
Technical Data
|
|
|
|
MODEL |
RPVE
20454 (2046)3 |
RPVE
20554 (2056)3 |
RPVE
20754 (2076)3 |
RPVE
20954 (2096)3 |
|
Heat output |
kW |
39.4 (41) |
49.9(51.9) |
68.3(71) |
91(94.6) |
|
Gas consumption1 |
Nat. gas G20 |
m3/h |
4.76 |
6.1 |
8.3 |
11 |
| |
Propane G31 |
kg/h |
3.56 |
4.51 |
6.18 |
8.25 |
| |
Butane G30 |
kg/h |
3.64 |
4.61 |
6.31 |
8.42 |
|
Gas connection2 |
Rc |
3/4 |
3/4 |
3/4 |
3/4 |
|
Airvolume @ 15°C |
m3/h |
4500 |
5500 |
7300 |
9800 |
|
Fan motor rating |
kW |
0.55 |
1.1 |
1.1 |
1.5 (2.2)5 |
|
Electrical supply |
|
415V 3N~50Hz |
|
Total electrical rating6 |
kW |
0.74 |
1.49 |
1.49 |
2.03 |
|
Approx weight |
kg |
155 |
190 |
215 |
280 |
Note:
1. Natural gas G20-Calorific value 10.48 kWh/m3 GCV, 15°C
1013mbar. Propane G31-Calorific value 14.0 kWh/kg GCV. Butane G30,
calorofic value 13.7 kWh/kg GCV.
2. Not supply line size.
3. Higher Efficiency Model.
4. For low NOx models change 0 to 5 e.g. 2545
5. For low NOx model only.
6. Increased by 900W during start up (± 30 seconds).
|
|
|
Dimension Data
|
|
|

Click the image for a close up view. Use the browser
BACK button to return.
|
|
|
|
MODEL |
RPVE 2045 |
RPVE 2055 |
RPVE 2075 |
RPVE 2095 |
|
Cabinet width |
A |
781 |
921 |
1131 |
1411 |
|
Duct outlet spigot width |
B |
570 |
710 |
920 |
1200 |
|
|