Reznor RPV 2000 units are fully automatic
gas fired heaters designed for larger industrial and
commercial applications, particularly where combined
heating and ventilation is required. At the heart of
each heater is the perfectly co-ordinated combination of
heat exchanger and burner, developed and patented by
Reznor, that has set the standard for efficiency,
reliability and operational life. Thermal efficiencies of
up to 91% based on net calorific value.
Units
are simple to install, and are supplied complete and
mounted on a base frame. An integral fan assisted flue
exhausts the products of combustion and at the same time
induces a precise amount of combustion air.
External
weatherproof units have a factory fitted flue outlet and
combustion air inlet and require only connection to gas
and electrical supplies. Internal units need connection
to a suitable flue system.
A
comprehensive range of options allows the heaters to be
tailor made to suit a wide variety of applications.
Reznor
microprocessor energy controls are available to
complement the energy efficient heaters and optimise fuel
economy.
RPV 2000 heaters are designed
for outdoor installation. RPVE units are supplied with an
insulated downturn discharge cabinet for rooftop
applications using 100% recirculated air. For
applications using full fresh air or combined fresh and
recirculation air, RPVJ units are provided with an
additional air intake complete with water separator.
The
units are also available without the downturn cabinet to
suit different external applications.
RPV
2000 units are available in seven sizes with heat outputs
between 23 and 95kW and airflows from 1350 to 12000m3/h
STANDARD
FEATURES
Units
suitable for natural gas
Stainless steel heat exchanger
(AISI 409)
Single stage burner control
Automatic ignition
Insulated cabinets
Fan assisted flue
Galvanised base frame
Constant air volume
OPTIONAL
ITEMS
Units
suitable for LPG
Stainless steel heat exchanger
(AISI 316)
Two stage or fully modulating
control
Filters
Dirty filter indication
Airflow proving indication
Roof curb
Variable air volume
Fresh air/return air
dampers
Manual two position or motorised
modulating damper actuators
Low NOx units
SPECIFICATION
RPV 2000
CABINETS
Cabinets
are manufactured from pre-painted galvanised steel and
are mounted on a galvanised steel base frame. Fan
cabinets and downturn cabinets are fully insulated.
RPVJ
models are supplied with a fresh air intake hood complete
with a water separator.
HEAT
EXCHANGER
Patented
Thermocore venturi tube assembly with precision matched
burners provides optimum efficiency and enhanced
operational life.
Standard
units are fitted with heat exchangers manufactured from
stainless steel (AISI 409).
Where
chlorinated vapours or certain contaminants may be
present 316 grade stainless steel heat exchangers must be
used, consult Reznor for such applications.
GAS
& SAFETY CONTROLS
All
units are tested and certified to current European
standards and CE marked.
A
multifunctional gas control valve complete with dual shut
off valves and a fully automatic ignition system provides
full safety monitoring of the heater operation. Automatic
ignition provides improved reliability.
Fan
operation is controlled by an integral fan control
thermostat, a constant fan option may be specified for
ventilation operations.
A
limit thermostat monitors the operation of the heaters
and shuts down the heater in the event of overheating or
air flow failure. For additional safety all Reznor units
are fitted with dual safety limit controls.
AIR
HANDLING
Fan
sections are fitted with double inlet forward curved
centrifugal blowers and a belt drive with an adjustable
pulley fitted to the motor to allow small on-site
adjustments to be made. Motors may be single or three
phase depending on the duty requirements up to 400Pa
resistance.
INSTALLATION
Installation
must be carried out by a CORGI registered installer in
accordance with the manufacturers instructions.
Standard
RPVE and RPVJ units are supplied with downturn discharge
cabinets (complete with duct spigot) for
"rooftop" installation. For alternative
installations where a duct outlet spigot is required,
units should be ordered "without downturn
cabinet".
The
units are provided complete with an integral fan assisted
flue outlet terminal and combustion air inlet grills. The
flue outlet, air inlet and controls access are supplied
as standard on the left hand side (LHS) (viewed in
direction of airflow) for opposite handed units specify
"RHS Controls". A gas isolation valve must be
fitted adjacent to each unit. An electrical isolator is
also required but the electrical supply to the units
should not be switched off except for maintenance.
Controls must be wired to the appropriate time and
temperature terminals and must not switch the main
electrical supply otherwise the control sequence of the
heater will be affected.
RPV
2000 Technical Data
| Model |
|
|
RPV
2025 |
RPV
2030 |
RPV
2035 |
RPV
2045 |
RPV
2055 |
RPV
2075 |
RPV
2095 |
| Heat output |
|
kW |
22.8 |
27.8 |
33.7 |
39.4 |
49.39 |
68.3 |
91 |
| Gas
consumption1 |
Nat Gas G20 |
m3/h |
2.75 |
3.36 |
4.1 |
4.76 |
6.1 |
8.3 |
11 |
| |
Propane G31 |
kg/h |
2.06 |
2.52 |
3.05 |
3.56 |
4.51 |
6.18 |
8.25 |
| |
Butane G30 |
kg/h |
2.1 |
2.6 |
3.12 |
3.64 |
4.61 |
6.31 |
8.42 |
| Gas
connection2 |
|
Rc |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
| Air volume
at 15oC |
Min |
m3/h |
1350 |
1650 |
2000 |
2300 |
2900 |
4000 |
5400 |
| |
Max |
m3/h |
3000 |
4000 |
5000 |
5000 |
7200 |
9000 |
12000 |
| |
Min |
kW |
0.18 |
0.18 |
0.18 |
0.18 |
0.25 |
0.25 |
0.25 |
| |
Max |
kW |
1.1 |
1.1 |
1.5 |
1.5 |
2.2 |
3 |
3 |
| |
|
kW |
Motor rating plus 0.15kW |
| Approx.
weight |
RPVE |
kg |
216 |
256 |
290 |
290 |
319 |
389 |
476 |
| |
RPVJ |
kg |
264 |
305 |
341 |
341 |
373 |
448 |
549 |
Appliances
with higher efficiency
| Model |
|
|
RPV
2026 |
RPV
2031 |
RPV
2036 |
RPV
2046 |
RPV
2056 |
RPV
2076 |
RPV
2096 |
| Heat output |
|
kW |
23.7 |
28.8 |
35 |
41 |
51.9 |
71 |
94.6 |
DIMENSION
DATA
RPVE (without downturn cabinet)
dimension diagram
RPVE dimension diagram
RPVJ dimension diagram
| Model |
|
RPV
25/26 |
RPV
30/31 |
RPV
35/36 |
RPV
45/46 |
RPV
55/56 |
RPV
75/76 |
RPV
95/96 |
| Cabinet
width |
A |
520 |
590 |
730 |
730 |
870 |
1080 |
1360 |
| Overall
width including base frame |
B |
558 |
628 |
768 |
768 |
908 |
1118 |
1398 |
| Duct outlet/inlet
(E&J) |
C |
370 |
440 |
580 |
580 |
720 |
930 |
1210 |
| Duct Outlet |
F |
360 |
430 |
570 |
570 |
710 |
920 |
1200 |
| All