hvac, space heaters, heaters, industrial, space heating, heating systems

heat, hvac, space heaters, propane heaters, heating, swimming pool heaters, reznor
l l l l l l
  Qualified for Energy Technology List - www.eca.gov.uk
 
 
   
 

The Reznor range of oil fired unit heaters is suitable for a wide variety of commercial and industrial applications. At the heart of these units there is a high efficiency stainless steel primary and secondary heat exchanger. This enables thermal efficiencies of over 90% to be achieved.

A high capacity axial fan ensures optimum air distribution. Both 70 and 100 models are fitted with multiple fans with the facility to relocate one fan to provide two way air distribution.

Units are available in four heat outputs 32, 40, 70 and 100kW and they offer the following benefits:

High thermal efficiencies help to reduce running costs.
Optimum air distribution at low noise levels.
Space saving - all units can be either suspended or base mounted thereby freeing up floor space for production or storage requirements.
Low installation costs - with high thermal efficiencies - over 90%
all units are eligible for Enhanced Capital Allowances.
Two way air distribution (70 and 100kW models only) allow units
to be centrally located with air distributed in opposite directions.
 
Optional Equipment
 
A range of options are also available. These include:
Electro thermolink fire valve sensors, combusion air adaptors, remote control panel c/w lockout reset and summer fan only facility, oil transfer pump or lifter.

Specification

Heat Exchanger
 
The high efficiency heat exchanger is designed for both long operational life and to have minimal resistance to airflow through the unit.
 
Air Handling
 
A quiet powerful axial fan provides high air flow through a series of adjustable horizontal louvres. It is also possible to reverse the direction of the airflow by modifying the position of the adjustable warm air discharge louvre and the axial fan.
 
Cabinets
 
Cabinets are constructed from zinc coated steel panels, finished in white epoxy powder coating paint.
 
 
Controls
 
All unit heaters have been designed for fully automatic operation and are available with optional remote control panels.
Installation
 
The units are suitable for suspended applications or may alternatively be mounted on a flat non combustible surface.
An oil fired valve must be installed external to the building where required in accordance with BS 5410:Part 2:1978.
Maximum oil lift is 3.5m (based on a 2 pipe system) which does not include for any oil pipe fittings.
Each heater is supplied with a flue tee piece section suitable for single wall stainless steel flue pipe.
Units must NOT be installed in atmospheres containing highly flammable vapours, combustible dust, halogenated hydrocarbons or chlorinated vapours.
A single phase electrical supply is required for each unit. This supply should NOT be switched off except for maintenance.
 
MODEL ROFSU 32 ROFSU 40 ROFSU 70 ROFSU 100
Heat output kW 31.6 39.7 70.2 99.3
Throw m 12 15 18 22
Air flow (T 15°C) m³/h 3100 3500 6200 9500
Temperature rise °C 28 31 31 29
Flue diameter mm 127 127 152 178
Electrical supply 230 volt 1 phase
Weight kg 85 91 137 177


Dimensions


MODELS A B C
ROFSU 32 723 610 120
ROFSU 40 723 610 120
ROFSU 72 1303 1190 150
ROFSU 100 1883 1770 180
 

 

 

Tel.. 01303 259141

Fax.. 01303 850002

sales@reznor.co.uk