Products
 
Free Standing Cabinet Warm Air Heaters
 
  CABINET HEATERS

The Reznor free standing range of cabinet warm air heaters combine innovative design techniques and proven heat exchange technology to produce units that are cost effective, efficient and aesthetically pleasing.

Ten model sizes cover heat outputs from 31kW to 289kW and are available as free standing vertical units or, alternatively, as horizontal units.

  Gas or oil fired
  Four pass heat transfer for improved thermal efficiency
  Heat exchanger tubes are expanded into collection boxes, eliminating possibility of weld failure
  Combustion chamber/heat exchanger assembly is flexibly mounted to allow for thermal expansion
  Double skin pentapost construction incorporating air cooled heat shield 
  Time switch and thermostats are pre-wired on vertical models to reduce installation costs
  . Freeblowing or ducted air distribution
OPTIONS
inlet duct spigots
Combustion air adaptors
Stainless steel heat exchangers
Increased fan duty
Flat-on air inlet filters
High/low burners
Four way louvred head
constant run fan relay

SPECIFICATION
HEAT EXCHANGER

The combustion chamber is manufactured from high quality heat resisting stainless steel and has a large surface area and volume to avoid localised hot spots and to ensure long life. A tubular cross flow heat exchanger provides excellent fuel economy and the heat exchanger tubes are expanded into the collection boxes thereby eliminating the possibility of weld failure.
The complete assembly is mounted to allow for thermal expansion to counteract the effect of thermal stress.


AIR HANDLING

Double inlet high efficiency centrifugal fans circulate air across all the heated surfaces to give low surface temperatures and maximise efficiency. Fans on models 29-1 to 88-1 are direct driven using a single phase motor. All other models are driven by a heavy duty three phase motor and v-belt system. Air discharge is via nozzle outlets, or a four way louvred head. Alternatively units may be installed with a fully ducted distribution system. 


CABINETS

The cabinets are constructed using a full pentapost frame and double skinned panels with an inner galvanised steel skin. All panels are easily removed for servicing.
Units are finished in a durable two tone powder paint. Four mounting feet are incorporated into the cabinet to ease on site handling. After location, these feet may be removed or left in position to raise the air inlet away from the floor to minimise the ingress if dust


FUEL

Heaters are available to operate on either natural gas (G20), Propane (G31), 28 or 35 sec oil. Gas fired units are fitted with a fully automatic forced draught burner complete with full safety controls and the heaters are tested and approved to the relevant CE standards. Oil fired models are supplied complete with a fully automatic forced draught pressure jet oil burner complete with safety controls and matched to each heater for optimum flame shape and efficiency.


CONTROLS

A combined fan and limit thermostat is fitted on all heaters, which delays fan start-up until the heat exchanger has reached operating temperature and continues to run the fan after the burner switches off until the remaining heat is dissipated. In the event of overheating, the unit would automatically be shut down by the limit thermostat.
On vertical models, time and temperature controls comprising digital time switch, room thermostat and frost thermostat, are pre-wired to the heater to simplify installation. Horizontal models are supplied with separate remote panel. Remote panels may also be supplied as an optional alternative on vertical models.


VERTICAL & HORIZONTAL CABINET HEATERS - TECHNICAL DATA

MODEL FSG/FSO*

29-1

44-1

60-1

88-1

117-3

150-3

175-3

205-3

235-3

293-3

Nominal output

kW

31

44

61

88

119

149

178

205

234

289

Gas Rate

Nat gas G20

m3/h

3.6

5.5

7.3

10.9

14.5

18.2

21.8

25.4

29.1

35.8

 

Propane G31

kg/h

2.7

4.1

5.4

8.2

10.9

13.6

16.3

19.0

21.7

26.8

Min. inlet pressure Natural Gas

mbar

17.5

17.5

17.5

17.5

17.5

17.5

17.5

17.5

17.5

17.5

Gas connection size1

Rc

1/2

1/2

3/4

3/4

3/4

3/4

3/4

11/4

11/4

11/4

Oil consumption

l/h

3.5

5.2

6.9

10.4

13.8

17.3

20.8

24.2

27.6

34.5

Oil connection size1

Rc

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

3/8

Air flow @ 15°C

m3/h

2500

2500

5180

5180

7140

8750

10500

12800

14100

17330

Temperature rise

C

36

52

34

50

49

50

50

47

49

49

Approximate throw

m

18

18

21

21

20

25

25

30

25

30

Number of nozzles

 

2

2

3

3

4

4

4

4

4

4

Available static pressure2

Pa

95

95

130

130

125

150

200

95

160

250

Electrical supply

230/240V/lPh~/50hz

400/415V/3Ph~/50hz

Main fan motor

kW

0.55

0.55

0.74

0.74

1.50

2.20

3.00

4.00

4.00

5.50

Burner motor

W

70

70

70

70

90

90

90

250

250

250

Total electrical rating

kW

0.91

0.91

1.60

1.60

2.41

2.76

4.60

5.80

5.47

8.39

Running current

Amps

3.4

3.4

6.6

6.6

2.3

3.7

5.5

8.3

7.0

12.0

Noise level @ 5 metres3

dB (A)

52

52

53

53

59

61

61

65

63

67

Maximum weight4

kg

190

190

225

225

280

292

300

320

360

380

Notes:

* FSG for Gas Fired, FSO for Oil Fired. Add suffix D for ducted models.
1. Not supply line size.
2. For alternative airflows or static pressure consult Reznor
3. Typical factory application.
4. Includes unit, burner and nozzles
NB. For maximum mounting heights on horizontal units, consult Reznor

VERTICAL CABINET HEATERS - DIMENSION DATA

Model 29-1/44-1
60-1/88-1
117-3/150-3
175-3/205-3
235-3/293-3
Cabinet height A1 1804 1804 2012 2073 2012
Overall height A2 2088 2168 2376 2477 2466
Overall width B 865 865 795 1186 1186
Cabinet depth C1 613 859 1158 1305 1504
Overall depth C2 928 1174 1473 1675 1874
Bottom to burner centre D 1007 1019 1041 1184 1112
Bottom to flue centre E 1441 1465 1637 1750 1678
Side to burner centre F 433 433 398 593 593
Duct outlet depth/ side duct inlet depth1 G 513 759 1058 1205 1404
Duct outlet width/rear duct inlet width 1 H 765 765 695 1086 1086
Duct inlet height1 K 445 516 600 711 600

Note 1: Normal dimensions. For specific ductwork connection drawings, please consult Reznor

HORIZONTAL CABINET HEATERS - DIMENSION DATA

Model 29-1/44-1
60-1/88-1
117-3/150-3
175-3/205-3
235-3/293-3
Cabinet length A1 1804 1804 2012 2073 2012
Overall height B 865 865 795 1186 1186
Cabinet depth C1 613 859 1158 1305 1504
Overall depth C2 928 1174 1473 1675 1874
Side to burner centre D 1007 1019 1041 1184 1112
Side to flue centre E 1441 1465 1637 1750 1678
Bottom to burner centre F 433 433 398 593 593
Duct outlet width/top duct inlet depth1 G 513 759 1058 1205 1404
Duct outlet height/rear duct inlet height1 H 765 765 695 1086 1086
Top duct inlet width1 K 445 516 600 711 600
Horizontal nozzle outlet length1 L 315 315 315 370 370
Hanger point depth M 560 806 1105 1252 1451
Hanger point width N 1751 1751 1959 2020 1959
Hanger point side to centre P 1258 1187 1311 1261 1311

Note 1: Normal dimensions. For specific ductwork connection drawings, please consult Reznor

 

Tel.. 01303 259141

Fax.. 01303 850002

sales@reznor.co.uk

An Ambi-Rad Group Company