CABINET HEATERSThe Reznor free
standing range of cabinet warm air heaters combine
innovative design techniques and proven heat exchange
technology to produce units that are cost effective,
efficient and aesthetically pleasing.
Ten
model sizes cover heat outputs from 31kW to 289kW and are available as free
standing vertical units or, alternatively, as horizontal units.
| |
|
Gas
or oil fired |
| |
|
Four pass heat transfer for improved thermal efficiency |
| |
|
Heat exchanger tubes are expanded into collection boxes,
eliminating possibility of weld failure |
| |
|
Combustion
chamber/heat exchanger assembly is flexibly
mounted to allow for thermal expansion |
| |
|
Double
skin pentapost construction incorporating air cooled heat shield |
| |
|
Time
switch and thermostats are pre-wired on vertical models to
reduce installation costs |
| |
. |
Freeblowing or ducted air distribution |
|
|
OPTIONS |
|
|
inlet duct spigots |
|
|
Combustion air adaptors |
|
|
Stainless steel heat exchangers |
|
|
Increased fan duty |
|
|
Flat-on air inlet filters |
|
|
High/low burners |
|
|
Four way louvred head |
|
|
constant run fan relay |
SPECIFICATION
HEAT EXCHANGER
The
combustion chamber is manufactured from high quality heat
resisting stainless steel and has a large surface area
and volume to avoid localised hot spots and to ensure
long life. A tubular cross flow heat exchanger provides
excellent fuel economy and the heat exchanger tubes are
expanded into the collection boxes thereby eliminating
the possibility of weld failure.
The complete assembly is mounted to allow for thermal
expansion to counteract the effect of thermal stress.
AIR HANDLING
Double inlet high efficiency centrifugal fans circulate air across all the
heated surfaces to give low surface temperatures and
maximise efficiency. Fans on models 29-1 to 88-1 are direct driven using
a single phase motor. All other models are driven by a heavy duty three
phase motor and v-belt system.
Air discharge is via nozzle outlets, or a four way louvred head.
Alternatively units may be installed with a fully ducted
distribution system.
CABINETS
The cabinets are constructed using a full pentapost frame and double
skinned panels with an inner galvanised steel skin. All panels are
easily removed for servicing.
Units are finished in a durable two tone powder paint. Four mounting
feet are incorporated into the cabinet to ease on site handling. After
location, these feet may be removed or left in position to raise the air
inlet away from the floor to minimise the ingress if dust
FUEL
Heaters
are available to operate on either natural gas (G20), Propane (G31), 28
or 35
sec oil. Gas fired units are fitted with a fully
automatic forced draught burner complete with full safety
controls and the heaters are tested and approved to the
relevant CE standards. Oil fired models are supplied
complete with a fully automatic forced draught pressure jet oil burner
complete with safety controls and matched to each heater for optimum
flame shape and efficiency.
CONTROLS
A combined
fan and limit thermostat is fitted on all heaters, which
delays fan start-up until the heat exchanger has reached
operating temperature and continues to run the fan after
the burner switches off until the remaining heat is
dissipated. In the event of overheating, the unit would automatically be
shut down by the limit thermostat.
On vertical models, time and temperature controls
comprising digital time switch, room thermostat and frost
thermostat, are pre-wired to the heater to simplify
installation. Horizontal models are supplied
with separate remote panel. Remote panels may also be supplied as
an optional alternative on vertical models.
VERTICAL & HORIZONTAL CABINET HEATERS -
TECHNICAL DATA
|
MODEL FSG/FSO* |
29-1 |
44-1 |
60-1 |
88-1 |
117-3 |
150-3 |
175-3 |
205-3 |
235-3 |
293-3 |
|
Nominal output |
kW |
31 |
44 |
61 |
88 |
119 |
149 |
178 |
205 |
234 |
289 |
|
Gas Rate |
Nat gas G20 |
m3/h |
3.6 |
5.5 |
7.3 |
10.9 |
14.5 |
18.2 |
21.8 |
25.4 |
29.1 |
35.8 |
| |
Propane G31 |
kg/h |
2.7 |
4.1 |
5.4 |
8.2 |
10.9 |
13.6 |
16.3 |
19.0 |
21.7 |
26.8 |
|
Min. inlet pressure Natural Gas |
mbar |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
17.5 |
|
Gas connection size1 |
Rc |
1/2 |
1/2 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
11/4 |
11/4 |
11/4 |
|
Oil consumption |
l/h |
3.5 |
5.2 |
6.9 |
10.4 |
13.8 |
17.3 |
20.8 |
24.2 |
27.6 |
34.5 |
|
Oil connection size1 |
Rc |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
|
Air flow @ 15°C |
m3/h |
2500 |
2500 |
5180 |
5180 |
7140 |
8750 |
10500 |
12800 |
14100 |
17330 |
|
Temperature rise |
C |
36 |
52 |
34 |
50 |
49 |
50 |
50 |
47 |
49 |
49 |
|
Approximate throw |
m |
18 |
18 |
21 |
21 |
20 |
25 |
25 |
30 |
25 |
30 |
|
Number of nozzles |
|
2 |
2 |
3 |
3 |
4 |
4 |
4 |
4 |
4 |
4 |
|
Available static pressure2 |
Pa |
95 |
95 |
130 |
130 |
125 |
150 |
200 |
95 |
160 |
250 |
|
Electrical supply |
|
230/240V/lPh~/50hz |
400/415V/3Ph~/50hz |
|
Main fan motor |
kW |
0.55 |
0.55 |
0.74 |
0.74 |
1.50 |
2.20 |
3.00 |
4.00 |
4.00 |
5.50 |
|
Burner motor |
W |
70 |
70 |
70 |
70 |
90 |
90 |
90 |
250 |
250 |
250 |
|
Total electrical rating |
kW |
0.91 |
0.91 |
1.60 |
1.60 |
2.41 |
2.76 |
4.60 |
5.80 |
5.47 |
8.39 |
|
Running current |
Amps |
3.4 |
3.4 |
6.6 |
6.6 |
2.3 |
3.7 |
5.5 |
8.3 |
7.0 |
12.0 |
|
Noise level @ 5 metres3 |
dB (A) |
52 |
52 |
53 |
53 |
59 |
61 |
61 |
65 |
63 |
67 |
|
Maximum weight4 |
kg |
190 |
190 |
225 |
225 |
280 |
292 |
300 |
320 |
360 |
380 |
Notes:
* FSG for
Gas Fired, FSO for Oil Fired. Add suffix D for ducted
models.
1. Not
supply line size.
2. For alternative airflows or static pressure consult
Reznor
3. Typical factory application.
4. Includes unit, burner and nozzles
NB. For maximum mounting heights on horizontal units, consult Reznor
VERTICAL CABINET HEATERS - DIMENSION DATA
| Model |
29-1/44-1
 |
60-1/88-1
 |
117-3/150-3
 |
175-3/205-3
 |
235-3/293-3
 |
| Cabinet
height |
A1 |
1804 |
1804 |
2012 |
2073 |
2012 |
| Overall height |
A2 |
2088 |
2168 |
2376 |
2477 |
2466 |
| Overall width |
B |
865 |
865 |
795 |
1186 |
1186 |
| Cabinet depth |
C1 |
613 |
859 |
1158 |
1305 |
1504 |
| Overall depth |
C2 |
928 |
1174 |
1473 |
1675 |
1874 |
| Bottom to
burner centre |
D |
1007 |
1019 |
1041 |
1184 |
1112 |
| Bottom to
flue centre |
E |
1441 |
1465 |
1637 |
1750 |
1678 |
| Side to
burner centre |
F |
433 |
433 |
398 |
593 |
593 |
| Duct outlet
depth/ side duct inlet depth1 |
G |
513 |
759 |
1058 |
1205 |
1404 |
| Duct outlet
width/rear duct inlet width 1 |
H |
765 |
765 |
695 |
1086 |
1086 |
| Duct inlet
height1 |
K |
445 |
516 |
600 |
711 |
600 |
Note 1: Normal dimensions. For specific
ductwork connection drawings, please consult Reznor
HORIZONTAL
CABINET HEATERS - DIMENSION DATA
| Model |
29-1/44-1
 |
60-1/88-1
 |
117-3/150-3
 |
175-3/205-3
 |
235-3/293-3
 |
| Cabinet length |
A1 |
1804 |
1804 |
2012 |
2073 |
2012 |
| Overall height |
B |
865 |
865 |
795 |
1186 |
1186 |
| Cabinet
depth |
C1 |
613 |
859 |
1158 |
1305 |
1504 |
| Overall depth |
C2 |
928 |
1174 |
1473 |
1675 |
1874 |
| Side to
burner centre |
D |
1007 |
1019 |
1041 |
1184 |
1112 |
| Side to
flue centre |
E |
1441 |
1465 |
1637 |
1750 |
1678 |
| Bottom to
burner centre |
F |
433 |
433 |
398 |
593 |
593 |
| Duct outlet
width/top duct inlet depth1 |
G |
513 |
759 |
1058 |
1205 |
1404 |
| Duct outlet
height/rear duct inlet height1 |
H |
765 |
765 |
695 |
1086 |
1086 |
| Top duct inlet
width1 |
K |
445 |
516 |
600 |
711 |
600 |
| Horizontal
nozzle outlet length1 |
L |
315 |
315 |
315 |
370 |
370 |
| Hanger point
depth |
M |
560 |
806 |
1105 |
1252 |
1451 |
| Hanger point
width |
N |
1751 |
1751 |
1959 |
2020 |
1959 |
| Hanger point
side to centre |
P |
1258 |
1187 |
1311 |
1261 |
1311 |
Note 1: Normal dimensions. For specific
ductwork connection drawings, please consult Reznor
|